Industry Power System

IPS Series Industrial Power 30 KVA - 600 KVA

IPS Salient Advantages Over Conventional UPS
Content

Features of industrial application environment
Introduction of IPS technology
Comparison between IPS, UPS and EPS
Advantages and shining point of IPS
Application note
Features of industrial application environment

Under normal circumstance, the environment comparatively bad
High temperature, humidity, dust, corrosive gas, serious air pollution
Formidable disturbance of power grid
Comparison between industrial electricity and electricity in computer room


Item
Industrial electricity
Electricity in computer room
Electric power
big, usually several hundreds KVA
Usually within 200KVA for Small and middle computer room; perhaps up to300-500KVA for large computer room
Load type
linear load such as sensitive , capacitive loads
also non-linear load such as computer
Computer load
Power supply system
for 3 phase electric machine, 3 phases 4 wires without Neutral;
for 1 phase load, 1 phase 3 wires
3 phases 5 wires ;
1 phase 3 wires
Voltage fluctuation
caused by large power equipment's startup and shutdown
caused by non-linear load such as computer
Neutral line current
Neutral line current shall not exceed 25% of rated current under low voltage
The imbalance degree of three-phase load should be less than 20%. But thanks to the non-linear load such as computer, even three phase balance, the Neutral line current can still reach above 50%.
Influence of power off
stop production, faulty products, damaged equipment
Communication interruption, damaged computer
Temperature
5~50 °C,even more than 60 °C
20~30 °C
cleanness
dusty,maybe corrosive gas
clean

Disadvantages of General UPS application

Power grid adaptability
bad adaptability to power grid fluctuation; feature: high frequency, line interactive
problem of compatible with generator
Environment adaptability
easily affected by drop and corrosive gas
Load adaptability
problem of configuration with generator load
impact to power when starting up or shutting down the loads
Economic problem
electricity expending
maintenance cost
Introduction of IPS technology

IPS is not a UPS

Main problem to be solved:
Some power disturbance is necessary to occur because of inherent limitation in power generation,transmission and distribution system, and these unstable factors are sure to affect the enterprise’s production. To eliminate the power disturbance occurd during production process, we have designed new system which can solve the below problem:

electric fall or peak disturbance (take up 57% of electric disturbance)

utility off (take up 7% of electric disturbance)

over-voltage (take up 15% of electric disturbance)

impact (take up 21% of electric disturbance)



applied to protect key equipment in the production process


IPS power application


mainly applied to emergency power accident in industry accasion;
food, iron and steel, automobiles, ceramics, paper, plastics, glass, pharmaceuticals, coal, petroleum, chemical industry, electronics, machinery and electrical, semiconductor and other industries;
bearing processing, transmission, manufacturing production lines, manufacturing processes, industrial control systems, automation control, CNC machine tools (CNC), industrial automation, laboratory test equipment, monitoring system and other automated control and production occasions.


Industrial application Ceramic factory


IPS series product

Model
Capability
Model
Capability
FR-UK3330P
30KVA
FR-UK33160P
160KVA
FR-UK3340P
40KVA
FR-UK33200P
200KVA
FR-UK3350P
50KVA
FR-UK33300P
300KVA
FR-UK3360P
60KVA
FR-UK33400P
400KVA
FR-UK3380P
80KVA
FR-UK33600P
600KVA
FR-UK33100P
100KVA

1-High efficiency & Energy saving

The system efficiency is over than 98%, 70% power saved than traditional UPS power solution.

No air-condition cooling need, reduce the room demand, save the investment cost.

low operating cost

2-lower power electric computerization & electric energy cost
prolong the battery life-span, lower maintenance cost
lower fault rate
MTBFIPS=220,000 hours
MTBFUPS=10,000 hours
1:1compatible generator units
consider the charge, the recommend match is 1.25:1
3-Advance technology
DSP control technologies
Power device modular design
Intelligent battery management technology
Boost & Floating charge transfer automatically
Temperature compensation
Logic power redundancy design
Intelligent fan timing control
Manual-maintenance bypass design
Unique energy feedback disposal setting
More suitable to electric load

4-High environment adaptability

Ultra strong anti-impact and loading capability.
Adapt inductive loads such as electrical machinery, water pump etc.
Well match to the generator
Protection level: IP33
Optional accessories such as AVR, ATS, transducer etc. , to satisfy the customized need of the power system.

5-Simple management

Chinese and English LCD display
1000 records
Full function battery management
Charge or discharge: Boost and floating charge, two stage charge, temperature compensation, adjustable charging current, intelligent adjustment of battery discharging protection point
Standard configuration: RS232/RS485/dry connection
Based on TCP/IP monitor management group
Based on WAP wireless management
Intelligent multi-mode MMBM-2 battery management
None guard: start automatically when electronic on

6-Rich optional fittings

Acousto-optic alarming setting
MMBM- 2 management system
Energy feedback processor
Regulator AVR
Input redundancy switch ATS
Distribution cabinet
Transducer

physical parameter


Power(KVA
Dimension(mm
Weight
(Kg)
Width
Deep

Height

30
40
50
60
80
600
800
1600
400
480
550
600
750
100
160
200
300
1200
800
1600
1060
1450
1600
2000
400
600
2400
800
1600
2500
3600

Comparison between IPS and online UPS


Item
IPS
Online UPS
Design concept
Industrial application
Computer room
Power supply system 3 phases 5 wires(3*L+1*N+1*G),
3 phases 5 wires (3*L+1*N+1*G),
System effeciency 98%
93%(6 pulse)/ 92%(12 pulse)
Configuration with motor load
1:1
4:1
Structure
Modular structure
Decentralized structure / modular structure
Control technology
DSP control
MCU / DSP control
Heat
small
Double conversion , large heat
Over current capacity
High (thyristor power supply)
limited by IGBT,transformer,inductor (inverter power supply)
MTBF
without rectifier, MTBF 120000 hours more than UPS
100000 hours
Generator compatible
1.25:1
2~2.5:1
Special options
electrical energy feedback aborsption device
null
Protection level
IP33
IP20 / IP21
Switch time
=4ms
0
Backup time
5mins-30mins
configured according to need

Comparison between IPS and EPS
Item IPS EPS
Design concept DSP control,quick processing speed
simulated control or MCU control, slow switch speed
Switch time 4ms,uninterruptible power supply 25-5000ms,power supply interrupted
Inverter synchronous control
real-time synchronization, switch (first connect then close) no, switch( first close then connect)
inverter mode Start state Close state
logical power redundancy yes no
application environment industry environment, applied to motor load fire prevention facilities, emergency lighting, not applied to motor load
Patrolled system yes no
configured with motor 1:1 4:1
electric energy feedback electric energy feedback absorption device no solution
Protection level IP33 IP20/IP21

IPS is not UPS, why?

UPS classification and working mode
Offline UPS, line interactive UPS, online UPS
Under utility state, the inverter of offline UPS is closed; the inverter of line interactive UPS is working as a charger; the inverter of online UPS is working with full power output
Main differences between IPS and UPS
Under utility state, IPS inverter starts ,standby and in the follow state, which is quite different from any working mode of UPS.
Own the function of electric energy feedback absorption which UPS do not have.
IPS protection level reaches IP 33.
Configured with motor load, IPS 1:1 UPS 4:1.

IPS Advantage & sale-points of IPS

Sale-points

Green environmental protest ?High efficiency energy saving ?total efficiency up to 98%, lower operating cost
 •
High system efficiency, only 2% power loss during operating, energy saving obviously in the high power supply situation industrial manufacture, considerable operating cost saved for enterprise users each year.
Stronger load ability
At normal, the utility supply power through thyristor, compare to UPS inverter with IGBT output, much stronger anti-impact and load capability.
Match to electronic load, don’t need to consider the capability obligating
• 
NO problem of LC balance: output through the isolation transformer after filtering by the inverter LC filter, no effected by the generator inductive load..
Especially suitable for industrial automatically manufacture situation, more safety & credibility.
IP33 is more suitable to industrial environment
Special design of machine energy feedback absorbing equipment
IPS operating cost
Item IPS UPS
Power
300KVA
300KVA
Active power 240KW 240KW
Operating cost
Efficiency
98% 93%
Power loss (KW)
4.8KW 16.8KW
Operation time per year (H)
8760 8760
(Power loss per year KWH)
42048KWH
147168KWH
Electric charge (?) 0.8 0.8
Electrovalence per year (?)
33638.40 117734.40
It’s obvious that adopt IPS industrial power system, could not only enjoy the safty power supply, but also reduce much electric cost than UPS, then high return-rate of investment.

Advantage of IPS application
High efficiency up to 98% (lower electric expenditure)
longer MTBF
Higher credibility
Longer life-span
Non-air condition cooling system (lower heat fevering)
Lower operation maintenance cost
  
Application note
About the output precision
At utility normal, IPS is direct, for it mainly supply to the industrial load. In the industry environment, much loads, include the generator etc., which are supplied directly by the utility originally. There is no disposal need for the voltage when adopting IPS, especially no request for voltage stability of the IPS, which with transducer. So at utility situation, output=input.
Disposal of voltage, such as on-line UPS double conversion, output voltage precision is very high, but also high power loss.
Few load ask for high voltage precision, could adopt UPS local protection, that is solution of IPS+UPS.
About switch time
IPS need 4ms switch time that is safe to industry loads, truly realizing uninterruptible.
When the power supply stops, due to inertia, motor continue to rotate within 10ms.
Computer load still can bear the feedback energy within 10ms because of energy storage capacitor.
About electric energy feedback
When the power supply stops (power shutdown), motor continues to rotate due to inertia, resulting in feedback energy whose instantaneous release would add to power/UPS/IPS or other loads and perhaps damage equipment because of high voltage. So IPS equipment has feedback energy absorption device. But for the application of large power motor, the configuration of transducer and feedback energy device should be considered.
There is device similar to feedback energy absorption device inside transducer.
About long backup time and battery configuration
IPS supply the backup time within 30 minutes.
If long backup time needed, load and environment temperature should be considered.
more than 30 minutes, IPS load be controlled within 50%
Standard temperature 0~40 °C,if the application environment with 40~50 °C, IPS load be controlled within 50%.
Lengthen backup time within 15~30 minutes, with general batteries.
Lengthen backup time within 10 minutes, with high-rate batteries.
About protection level
IPS protection level :IP33
Customize products of dampproof, dustproof requirement according to users’ need
Temporarily refuse the order of products of explosion-proof requirement
IP protection level consists of 2 figures. The first one shows the level that UPS keep away from dust and prevent intrusion; the second one shows the level of UPS’ moisture-proof and water-proof. Big figure means high protection level.

   The first figure 0 No protection
1 prevent the intrusion of more than 50 mm solid object
2 prevent the intrusion of more than 12 mm solid object
3 prevent the intrusion of more than 2.5 mm solid object
   The second figure 0 No protection
1 Prevent drip
2 prevent drip even with 15 degree bevel
3 Prevent rain or water with 60 degree bevel