Industry
Power System
IPS
Series Industrial Power 30 KVA
- 600 KVA
IPS
Salient Advantages Over Conventional
UPS
Content
Features
of industrial application environment
Introduction of IPS technology
Comparison between IPS, UPS
and EPS
Advantages and shining point
of IPS
Application note
Features of industrial application
environment
Under
normal circumstance, the environment
comparatively bad
High temperature, humidity,
dust, corrosive gas, serious
air pollution
Formidable disturbance of power
grid
Comparison between industrial
electricity and electricity
in computer room |
Item
|
Industrial
electricity
|
Electricity
in computer room
|
Electric
power
|
big,
usually several hundreds KVA
|
Usually
within 200KVA for Small and middle
computer room; perhaps up to300-500KVA
for large computer room
|
Load
type
|
linear
load such as sensitive , capacitive
loads
also non-linear load such as computer
|
Computer
load
|
Power
supply system
|
for
3 phase electric machine, 3 phases
4 wires without Neutral;
for 1 phase load, 1 phase 3 wires
|
3
phases 5 wires ;
1 phase 3 wires
|
Voltage
fluctuation
|
caused
by large power equipment's startup
and shutdown
|
caused
by non-linear load such as computer
|
Neutral
line current
|
Neutral
line current shall not exceed
25% of rated current under low
voltage
|
The
imbalance degree of three-phase
load should be less than 20%.
But thanks to the non-linear load
such as computer, even three phase
balance, the Neutral line current
can still reach above 50%.
|
Influence
of power off
|
stop
production, faulty products, damaged
equipment
|
Communication
interruption, damaged computer
|
Temperature
|
5~50
°C,even more than 60 °C
|
20~30
°C
|
cleanness
|
dusty,maybe
corrosive gas
|
clean
|
Disadvantages
of General UPS application
Power
grid adaptability
bad adaptability to power grid
fluctuation; feature: high frequency,
line interactive
problem of compatible with generator
Environment adaptability
easily affected by drop and
corrosive gas
Load adaptability
problem of configuration with
generator load
impact to power when starting
up or shutting down the loads
Economic problem
electricity expending
maintenance cost
Introduction of IPS technology
IPS
is not a UPS
Main
problem to be solved:
Some power disturbance is necessary
to occur because of inherent
limitation in power generation,transmission
and distribution system, and
these unstable factors are sure
to affect the enterprise’s
production. To eliminate the
power disturbance occurd during
production process, we have
designed new system which can
solve the below problem:
electric
fall or peak disturbance (take
up 57% of electric disturbance)
utility
off (take up 7% of electric
disturbance)
over-voltage
(take up 15% of electric disturbance)
impact (take up 21% of electric
disturbance)
applied to protect key equipment
in the production process
IPS power application
mainly applied to emergency
power accident in industry accasion;
food, iron and steel, automobiles,
ceramics, paper, plastics, glass,
pharmaceuticals, coal, petroleum,
chemical industry, electronics,
machinery and electrical, semiconductor
and other industries;
bearing processing, transmission,
manufacturing production lines,
manufacturing processes, industrial
control systems, automation
control, CNC machine tools (CNC),
industrial automation, laboratory
test equipment, monitoring system
and other automated control
and production occasions.
|
| Industrial
application |
Ceramic
factory |
 |
 |
Model
|
Capability
|
Model |
Capability
|
FR-UK3330P
|
30KVA
|
FR-UK33160P
|
160KVA
|
FR-UK3340P
|
40KVA
|
FR-UK33200P
|
200KVA
|
FR-UK3350P
|
50KVA
|
FR-UK33300P
|
300KVA
|
FR-UK3360P
|
60KVA
|
FR-UK33400P
|
400KVA
|
FR-UK3380P
|
80KVA
|
FR-UK33600P
|
600KVA
|
FR-UK33100P
|
100KVA
|
|
|
|
1-High
efficiency & Energy saving
The
system efficiency is over than
98%, 70% power saved than traditional
UPS power solution.
No
air-condition cooling need,
reduce the room demand, save
the investment cost.
low
operating cost
2-lower power electric computerization
& electric energy cost
prolong the battery life-span,
lower maintenance cost
lower fault rate
MTBFIPS=220,000 hours
MTBFUPS=10,000 hours
1:1compatible generator units
consider the charge, the recommend
match is 1.25:1
3-Advance technology
DSP control technologies
Power device modular design
Intelligent battery management
technology
Boost & Floating charge
transfer automatically
Temperature compensation
Logic power redundancy design
Intelligent fan timing control
Manual-maintenance bypass design
Unique energy feedback disposal
setting
More suitable to electric load
4-High
environment adaptability
Ultra strong anti-impact and
loading capability.
Adapt inductive loads such as
electrical machinery, water
pump etc.
Well match to the generator
Protection level: IP33
Optional accessories such as
AVR, ATS, transducer etc. ,
to satisfy the customized need
of the power system.
5-Simple management
Chinese and English LCD display
1000 records
Full function battery management
Charge or discharge: Boost and
floating charge, two stage charge,
temperature compensation, adjustable
charging current, intelligent
adjustment of battery discharging
protection point
Standard configuration: RS232/RS485/dry
connection
Based on TCP/IP monitor management
group
Based on WAP wireless management
Intelligent multi-mode MMBM-2
battery management
None guard: start automatically
when electronic on
6-Rich
optional fittings
Acousto-optic alarming setting
MMBM- 2 management system
Energy feedback processor
Regulator AVR
Input redundancy switch ATS
Distribution cabinet
Transducer
physical parameter |
| Power(KVA |
Dimension(mm |
Weight
(Kg) |
Width
|
Deep
|
Height
|
30
40
50
60
80
|
600
|
800
|
1600
|
400
480
550
600
750 |
100
160
200
300
|
1200
|
800
|
1600
|
1060
1450
1600
2000 |
400
600
|
2400
|
800
|
1600
|
2500
3600 |
|
Comparison
between IPS and online UPS |
Item
|
IPS
|
Online
UPS |
Design
concept
|
Industrial
application
|
Computer
room |
| Power
supply system |
3
phases 5 wires(3*L+1*N+1*G),
|
3
phases 5 wires (3*L+1*N+1*G), |
| System
effeciency |
98%
|
93%(6
pulse)/ 92%(12 pulse) |
Configuration
with motor load
|
1:1
|
4:1 |
Structure
|
Modular
structure
|
Decentralized
structure / modular structure |
Control
technology
|
DSP
control
|
MCU
/ DSP control |
Heat
|
small
|
Double
conversion , large heat |
Over
current capacity
|
High
(thyristor power supply)
|
limited
by IGBT,transformer,inductor (inverter
power supply) |
MTBF
|
without
rectifier, MTBF 120000 hours more
than UPS
|
100000
hours |
Generator
compatible
|
1.25:1
|
2~2.5:1 |
Special
options
|
electrical
energy feedback aborsption device
|
null |
Protection
level
|
IP33
|
IP20
/ IP21 |
Switch
time
|
=4ms
|
0 |
Backup
time
|
5mins-30mins
|
configured
according to need |
| Comparison
between IPS and EPS |
| Item |
IPS |
EPS |
| Design
concept |
DSP
control,quick processing speed
|
simulated
control or MCU control, slow switch
speed |
| Switch
time |
4ms,uninterruptible
power supply |
25-5000ms,power
supply interrupted |
Inverter
synchronous control
|
real-time
synchronization, switch (first
connect then close) |
no,
switch( first close then connect) |
| inverter
mode |
Start
state |
Close
state |
| logical
power redundancy |
yes |
no |
| application
environment |
industry
environment, applied to motor
load |
fire
prevention facilities, emergency
lighting, not applied to motor
load |
| Patrolled
system |
yes |
no |
| configured
with motor |
1:1 |
4:1 |
| electric
energy feedback |
electric
energy feedback absorption device |
no
solution |
| Protection
level |
IP33 |
IP20/IP21 |
| UPS
classification and working mode |
• |
Offline
UPS, line interactive UPS, online
UPS |
• |
Under
utility state, the inverter of
offline UPS is closed; the inverter
of line interactive UPS is working
as a charger; the inverter of
online UPS is working with full
power output |
| Main
differences between IPS and UPS |
• |
Under
utility state, IPS inverter starts
,standby and in the follow state,
which is quite different from
any working mode of UPS. |
• |
Own
the function of electric energy
feedback absorption which UPS
do not have. |
• |
IPS
protection level reaches IP 33. |
• |
Configured
with motor load, IPS 1:1 UPS 4:1. |
IPS
Advantage & sale-points of
IPS
Sale-points |
| Green
environmental protest ?High efficiency
energy saving ?total efficiency
up to 98%, lower operating cost |
| • |
High
system efficiency, only 2% power
loss during operating, energy
saving obviously in the high
power supply situation industrial
manufacture, considerable operating
cost saved for enterprise users
each year. |
| Stronger
load ability |
• |
At
normal, the utility supply power
through thyristor, compare to
UPS inverter with IGBT output,
much stronger anti-impact and
load capability. |
• |
Match
to electronic load, don’t
need to consider the capability
obligating |
• |
NO
problem of LC balance: output
through the isolation transformer
after filtering by the inverter
LC filter, no effected by the
generator inductive load.. |
| Especially
suitable for industrial automatically
manufacture situation, more safety
& credibility. |
• |
IP33
is more suitable to industrial
environment |
• |
Special
design of machine energy feedback
absorbing equipment |
| Item |
IPS |
UPS |
Power
|
300KVA
|
300KVA |
| Active
power |
240KW |
240KW |
| Operating
cost |
Efficiency
|
98% |
93% |
Power
loss (KW)
|
4.8KW |
16.8KW |
Operation
time per year (H)
|
8760 |
8760 |
(Power
loss per year KWH)
|
42048KWH
|
147168KWH |
| Electric
charge (?) |
0.8 |
0.8 |
Electrovalence
per year (?)
|
33638.40 |
117734.40 |
It’s
obvious that adopt IPS industrial
power system, could not only
enjoy the safty power supply,
but also reduce much electric
cost than UPS, then high return-rate
of investment. |
| Advantage
of IPS application |
• |
High
efficiency up to 98% (lower electric
expenditure) |
• |
longer
MTBF |
• |
Higher
credibility |
• |
Longer
life-span |
• |
Non-air
condition cooling system (lower
heat fevering) |
• |
Lower
operation maintenance cost |
| |
Application
note
|
| About
the output precision |
• |
At
utility normal, IPS is direct,
for it mainly supply to the
industrial load. In the industry
environment, much loads, include
the generator etc., which are
supplied directly by the utility
originally. There is no disposal
need for the voltage when adopting
IPS, especially no request for
voltage stability of the IPS,
which with transducer. So at
utility situation, output=input. |
• |
Disposal
of voltage, such as on-line
UPS double conversion, output
voltage precision is very high,
but also high power loss. |
• |
Few
load ask for high voltage precision,
could adopt UPS local protection,
that is solution of IPS+UPS. |
| About
switch time |
• |
IPS
need 4ms switch time that is safe
to industry loads, truly realizing
uninterruptible. |
• |
When
the power supply stops, due to
inertia, motor continue to rotate
within 10ms. |
• |
Computer
load still can bear the feedback
energy within 10ms because of
energy storage capacitor. |
| About
electric energy feedback |
• |
When
the power supply stops (power
shutdown), motor continues to
rotate due to inertia, resulting
in feedback energy whose instantaneous
release would add to power/UPS/IPS
or other loads and perhaps damage
equipment because of high voltage.
So IPS equipment has feedback
energy absorption device. But
for the application of large
power motor, the configuration
of transducer and feedback energy
device should be considered. |
• |
There
is device similar to feedback
energy absorption device inside
transducer. |
| About
long backup time and battery configuration |
• |
IPS
supply the backup time within
30 minutes. |
• |
If
long backup time needed, load
and environment temperature should
be considered. |
|
| • |
more
than 30 minutes, IPS load
be controlled within 50% |
| • |
Standard
temperature 0~40 °C,if
the application environment
with 40~50 °C, IPS
load be controlled within
50%. |
|
• |
Lengthen
backup time within 15~30 minutes,
with general batteries. |
• |
Lengthen
backup time within 10 minutes,
with high-rate batteries. |
| About
protection level |
• |
IPS
protection level :IP33 |
• |
Customize
products of dampproof, dustproof
requirement according to users’
need |
• |
Temporarily
refuse the order of products of
explosion-proof requirement |
| IP
protection level consists of
2 figures. The first one shows
the level that UPS keep away
from dust and prevent intrusion;
the second one shows the level
of UPS’ moisture-proof
and water-proof. Big figure
means high protection level. |
| The
first figure |
0 |
No
protection |
| 1 |
prevent
the intrusion of more than 50
mm solid object |
| 2 |
prevent
the intrusion of more than 12
mm solid object |
| 3 |
prevent
the intrusion of more than 2.5
mm solid object |
| The
second figure |
0 |
No
protection |
| 1 |
Prevent
drip |
| 2 |
prevent
drip even with 15 degree bevel |
| 3 |
Prevent
rain or water with 60 degree bevel |
|